Close Menu
  • Feature Articles
  • Digital Issues
  • News
  • Events
  • Products
  • Subscribe
  • Advertise
  • Videos
Facebook X (Twitter) Instagram
Trending
  • DiversiTech acquires Ditek
  • Nibco acquires UniTorq
  • Protected: Sponsored Article: The Copper Standard, Re-Engineered
  • Clean Hands Certified releases its 2026 handwashing index
  • Northwestern Polytechnic opens skilled trades training centre
  • Ont. invests in training skilled trades workers
  • Canada announces counter-tariffs on US-based HVAC/R equipment
  • Brookfield enters talks to acquire RWC
Facebook X (Twitter) Instagram LinkedIn YouTube RSS
Plumbing & HVAC
  • Feature Articles
  • Digital Issues
  • News
  • Events
  • Products
  • Subscribe
  • Advertise
  • Videos
Plumbing & HVAC
You are at:Home»Feature Articles»Variable speed ECM circulators

Variable speed ECM circulators

0
By Plumbing & HVAC Staff on March 19, 2024 Feature Articles
These smart pumps are quite obedient.

By John Barba, Rick Mayo, and Dave Holdorf

View the full presentation on “ECM Circulator Technology – The Myths and the Realities”

If you’re anything like me, the first thing that comes to mind when you think about variable speed circulators is the 1970s rock band Supertramp. No? Maybe you’re not like me. Either way, allow me to explain.

Supertramp’s 1979 hit “The Logical Song” is one of the decade’s best, with one of the greatest lines ever: “Watch what you say, or they’ll be calling you a radical.” Well, in hydronics, there is no radical, cynical, fanatical, or criminal. I guess there’s sometimes the fanatical, but that’s not the point.

The point is that hydronics is logical. It’s downright Spockian if you think about it. There’s a beautiful logic to how all your parts and pieces work, both on their own and especially in how they work together within the dynamics of the system.

However, when it comes to variable speed circulators, sometimes “The Logical Song” goes right out the window. All we’re left with is “Goodbye Stranger” and Mr. Spock on his every seven-year pon farr sabbatical back to Vulcan.

Let’s consider the logic behind variable speed circulators, both Delta-T and Delta-P. The prevailing attitude is that they always give you the right flow, no matter what. You can go ahead and call me a radical, but that’s not logical.

Intuitive pumps
For a variable speed circulator to always give you the right flow, it would have to have some way of knowing what the Btu/h load of each room and the system is at any given point in time. It would also need an idea of what the outdoor temperature is at any given point in time, as well as how much radiation is installed in each room. Spoiler alert: It doesn’t know any of those things.

For some reason, the industry has insisted on calling these things smart pumps. The reality, unfortunately, is they’re not all that smart. What they are, however, is obedient. For example, if you program a residential Delta-P circulator to operate in the constant pressure mode at 10 ft. of head, well then, by golly, that’s what it’s going to do. As zone valves open or close, the circulator will “feel” either less or more resistance against the impeller. Algorithms kick in and tell the circulator to either speed up or slow down.

The result is the circulator will always work at 10 ft. of head on what’s called the control curve. It’s the ultimate flat curve circulator.

For a variable speed circulator to always give the right flow, it would have to have some way of knowing what the Btu/h load of each room and the system is at any given point in time.

Use the same circulator in the same operating mode in a zone pump application and it will still work on its control curve. The difference, however, is it won’t vary its speed because there’s nothing in the single zone that will change resistance against the impeller. Once the circulator finds its happy place on the control curve, that’s where it will work because that’s where you told it to work.

Reduce over-pumping
Now, don’t read that as saying you shouldn’t use a variable speed pump as a zone pump. Far from it. The ability to program the circulator will allow you to set the speed to operate as closely to a zone’s flow and head requirement as possible. That can help reduce over-pumping, which leads to short cycling, which leads to all kinds of bad things.

If you set the circulator to proportional pressure (those funky-looking curves that slope down and to the left), the only thing that changes is the system will work on whichever funky curve you select.
In neither of these instances is the circulator giving you the right flow. If you program them accurately, you might get close.

And one more thing, in both applications, the circulator will run at the same speed in October or April as it does in January. Again, because that’s what you told it to do. Like I said, obedient.

Delta-T circulators will at least give you a fighting chance at the right flow. What a Delta-T circulator does is vary its speed in order to maintain the designed system Delta-T. If you design for a 20-degree Delta-T, well then give it a 20-degree Delta-T. Boilers like it, radiators like it, and systems like it.

As zones close, the system needs to take fewer Btu out of the water through the radiation. That makes the return water temperature want to increase (and the Delta-T, or temperature difference) decrease. The logic will tell the circulator to slow down to maintain the designed-for temperature difference. The opposite happens when zones open.

Delta-T circulator
Additionally, as the heat load changes with the weather, the circulator will continue to speed up or slow down to maintain the design for Delta-T. That is, until it can’t.

It’s the professional’s ability to think and to make sense of this technology that separates them from the handyperson.

At some point, the circulator will reach its minimum speed and logic dictates that you can’t go any slower than minimum, no matter what anyone says. The circulator won’t be able to maintain the design for Delta-T anymore. The good news, however, is it’ll still be wide enough to minimize bad things like short-cycling and higher-than-desirable return water temperatures to a modulating/condensing boiler.

Just about every variable speed pump manufacturer has a Delta-P circulator with an automatic function. And while it sounds cool, we do need to check in with Mr. Spock and Supertramp, as well as reality, to understand what auto really does.

It’s nice to think that slick little function does all the work for us and takes the thinking out of circulator selection. Unfortunately, that’s utter nonsense. It’s the professional’s ability to think and to make sense of all this technology that separates him from the handyperson. It takes a pro to understand how all these operating modes work and to select the right one for each job.

That slick little button does do a slick little job. However, for small residential circulators, that job is limited to continuous circulation applications with modulating thermostatic radiator valves and panel radiators. In that case, given time (like, a lot of time), the circulator will adjust its proportional pressure curve up or down if it experiences a significant change in overall flow (due to TRVs being mostly open or mostly closed) for a significant period of time (20 minutes up to an hour).

So, what’s the takeaway? It’s this: It’s important to understand how variable speed circulators work and what they do. There’s no magic involved. These things are logical and obedient. A poorly programmed variable speed circulator is, at best, an electricity saver. That’s not a bad thing at all, but a poorly programmed variable speed circulator is still an oversized circulator that limits the overall efficiency of a system.

But if you properly apply and program one of these babies, well, now you have a circulator that can help enhance the overall efficiency of a system. And that, mon ami, is a very good thing. If you don’t mind me saying, it’s pretty darned logical.

circulator pumps ECM circulators HVAC hydronic systems Plumbing Skilled Trades
Share. Facebook Twitter Pinterest LinkedIn Tumblr Email
Previous ArticlePCM batteries: packing a punch
Next Article Hybrid system

Related Posts

DiversiTech acquires Ditek

Nibco acquires UniTorq

Protected: Sponsored Article: The Copper Standard, Re-Engineered

Comments are closed.

About
About

Plumbing & HVAC

Canada's largest and most qualified circulation to the mechanical trades.

Subscribe Now!

Recent Posts
September 15, 2026

DiversiTech acquires Ditek

September 14, 2026

Nibco acquires UniTorq

September 11, 2026

Clean Hands Certified releases its 2026 handwashing index

Pages
  • Advertise
  • Feature Articles
  • Get in Touch
  • Heat Pump Sales Tool
  • News
  • Products
  • Subscribe
  • Videos
Copyright © 2024 Plumbing & HVAC all rights reserved | Designed and Developed by Upnorthwebs

Type above and press Enter to search. Press Esc to cancel.